ZW32-40.5 OUTDOOR HIGH VOLTAGE VACUUM CIRCUIT BREAKER (HIGH CURRENT)

Short Description:

ZW32-40.5 outdoor high voltage vacuum circuit breaker adopts a uniquely designed permanent magnet mechanism and a highly reliable intelligent controller.The device is mainly used in medium-voltage overhead line power grids, used for dividing and closing load current, overload current, and short-circuit current, and has 0 to 3 times of automatic reclosing.


Product Detail

Product Tags

Product Overview
   ZW32-40.5 outdoor high voltage vacuum circuit breaker adopts a uniquely designed permanent magnet mechanism and a highly reliable intelligent controller.

   The device is mainly used in medium-voltage overhead line power grids, used for dividing and closing load current, overload current, and short-circuit current, and has 0 to 3 times of automatic reclosing.
Functional characteristics
1.Extremely high reliability
2. Completely maintenance-free during the entire life span
3. It has high mechanical life and electrical life
4. The whole machine is small in size, light in weight and easy to install
5. With standard relay protection and fast automatic reclosing function
Main Technical Parameters

No. Item Unit Data
1 Rated voltage kV 40.5
2 Rated current A 1250/1600
3 Rated frequency Hz 50 或 60
4 Power frequency withstand voltage 1 min( wet)(dry) kV 80/95
5 Lightning impulse withstand current (peak) kV 185
6 Rated short-circuit breaking current kA 31.5
7 Rated short-circuit closing current (peak) kA 80
8 Rated peak withstand current kA 80
9 4s short-time withstand current kA 31.5
10 Rated Operating Cycle    open - 0.1s - close open - 3s - close open-6sclose open-60 srecover
11 Rated short-circuit current breaking time Times 30
12 Mechanical life Times 20000
13 Permanent magnet mechanism control voltage V DC220
14 Secondary circuit 1 min power frequency withstand voltage kV 2

 

Main mechanical parameters of circuit breakers

No. Item Unit Data
1 Contact opening distance mm 16±1
2 Contact overstroke mm 4±0.5
3 Opening speed m/s 1.4-1.8
4 Closing speed m/s 0.4-0.8
5 Contact closing bounce time ms ≤5
6 Center distance between phases mm 460±2
7 Different Periods of Three-phase Closing ms ≤2
8 Resistance of each phase conductive circuit μΩ < 120
9 Closing time ms 25 ~ 45
10 Opening time ms 20 ~ 45
11 Weight Kg 295

 