Welcome to our websites!
Tel/Whatsapp/Wechat: +86-15968734813, Email: alice@cnhighvolt.com

ZW20-12FOUTDOOR HIGH VOLTAGE VACUUM DEMARCATION CIRCUIIT BREAKER

Short Description:

ZW20-12F outdoor high voltage vacuum demarcation circuit breaker (watchdog switch) is an outdoor power distribution device with a rated voltage of 12kV and a three-phase AC 50Hz.When the user’s internal fault occurs in the T-type wiring of the 12kV distribution line, or although it occurs inside the user’s incoming switch, but its protection action time limit and the substation’s outgoing switch protection are improper, it will cause the substation’s outgoing switch protection to open. If the fault is permanent and the substation recloses unsuccessfully, an accident in the medium voltage user’s field will cause the entire distribution trunk to be out of power. This common spread accident in the power grid will cause significant losses to society. ZW20-12F outdoor high voltage vacuum demarcation circuit breaker (watchdog switch) is installed at the responsibility demarcation of the overhead power distribution line. The front end of the user’s incoming line will automatically remove the single-phase ground fault and inter-phase short-circuit fault within the user to avoid Faults in the user’s world spread to the main transmission line to ensure the safety of electricity use for non-faulty users and improve the reliability of electricity use


Product Detail

Product Tags

Product Overview

    ZW20-12F outdoor high voltage vacuum demarcation circuit breaker (watchdog switch) is an outdoor power distribution device with a rated voltage of 12kV and a three-phase AC 50Hz.

    When the user’s internal fault occurs in the T-type wiring of the 12kV distribution line, or although it occurs inside the user’s incoming switch, but its protection action time limit and the substation’s outgoing switch protection are improper, it will cause the substation’s outgoing switch protection to open. If the fault is permanent and the substation recloses unsuccessfully, an accident in the medium voltage user’s field will cause the entire distribution trunk to be out of power. This common spread accident in the power grid will cause significant losses to society.   

    ZW20-12F outdoor high voltage vacuum demarcation circuit breaker (watchdog switch) is installed at the responsibility demarcation of the overhead power distribution line. The front end of the user’s incoming line will automatically remove the single-phase ground fault and inter-phase short-circuit fault within the user to avoid Faults in the user’s world spread to the main transmission line to ensure the safety of electricity use for non-faulty users and improve the reliability of electricity use

Main Technical Parameters

No. Item Unit Data
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 Rated current A 630 1000
4 Rated short-circuit breaking current kA 20 25
5 Rated peak withstand current kA 50 63
6 Rated short-time withstand current kA 20 25
7 Rated short circuit switching current kA 50 63
8 Rated operation sequence    open-0.3s-close open-180s-close open
9 Mechanical life Times 10000
10 Rated current breaking times Times 10000
11 Rated short-circuiit breaking times Times 30
12 Frequency withstand voltage 1 min interphase, to earth kV 34
 interphase, to earth/Fracture kV 42/48
13 Lightning impulse withstand voltage  interphase, to earth/Fracture kV 75/85
14 Secondary circuit 1 min power frequency withstand voltage V 2000
15 Weight kg  140
16 Contact opening distance mm 9
17 Contact contacting stroke mm 3
18 Average opening speed m/s 1.2±0.2 +1-0.5
19 Average closing speed m/s 0.6±0.2 +1-0.5
20 rated operation voltage V AC/DC220
21 SF6 gas rated pressure (gauge pressure) MPa 0

Appearance And Installation Dimensions3