ZCW10-40.5OPEN TYPE COMBINATION APPLIANCES

Short Description:

ZCW10-40.5/T600-31.5 Open Type Combination Appliances is complete set of combined equipment, using air as insulation, SF6 gas as arc extinguishing medium, for controlling and protection of three- phase AC 40.5kV transmission and distribution systems, suitable for industrial and mining enterprises substation, mountain substation.


Product Detail

Product Tags

Product Overview
   ZCW10-40.5/T600-31.5 Open Type Combination Appliances is complete set of combined equipment, using air as insulation, SF6 gas as arc extinguishing medium, for controlling and protection of three- phase AC 40.5kV transmission and distribution systems, suitable for industrial and mining enterprises substation, mountain substation.
Working Environment
This product is an outdoor product and can also be used indoors.
The environmental conditions are as follows
1. Altitude: not more than 2000 meters;
2. Ambient temperature: -30℃ -+40℃ (special requirements -40℃ ~+40℃ );
3. Relative humidity: daily average is not greater than 95%, monthly average is not greater than 90%(25℃ );
4. Wind speed: no more than 35 m/s:
5. The pollution level is Ⅲ , the creepage distance of porcelain sleeve is greater than 1050mm (nominal creepage distancemore than 25mm/kV);
6. No flammable, explosive, chemical corrosion and severe vibration occasions;
7. Earthquake intensity: no more than 8 degrees;
8. The thickness of the ice shoes shall not exceed 10mm.

Main Technical Parameters

No. Item Unit Data
1 Rated voltage kV 40.5
2 Rated frequency Hz 50
3 Rated current A 1600
4 Rated short-time withstand current kA 31.5
5 Rated peak withstand current kA 80
6 Rated short circuit duration s 4
7 Rated insulation level Lightning shock withstand voltage (full wave peak)   185/215 (Fracture)
Power frequency withstand voltage (1 min)   95/118 ( Fracture)
8 Control circuit and auxiliary circuit voltage V DC110,220 AC220
9 Partial discharge pC 20
10 Interval width m 1.6 (general)
11 SF6 gas alarm pressure (20℃ )   0.45MPa
12 SF6 gas locking pressure (20℃ )   0.40MPa
13 Control circuit rated voltage   DC110 220 AC220
14 Annual air leakage rate of SF6 gases   ≤ 1%/  year
15 SF6 gas moisture content (20℃ )   ≤ 150(take over)μL/L
≤ 300(in service)μL/L
16 SF6 gas weight   7kg
17 Mechanical life   6000 times
18 Dynamic load Vertical upward   10000N
Vertical downward   12000N

Appearance And Installation Dimensions