Welcome to our websites!
Tel/Whatsapp/Wechat: +86-15968734813, Email: alice@cnhighvolt.com

LW -252 SULFUR HEXAFLUORIDE CIRCUIT BREAKER INTERGRATEDTYPE(SPLITTYPE)

Short Description:

LW □ -252/4000-50 self-energy AC high-voltage sulfur hexachloride circuit breaker for outdoor products, applicable toaltitude not exceeding 2000 m, ambient temperature not less than-30 ℃ , AC 50 Hz of the area where the pollution level is not higher than level IV, in the grid with a maximum voltage of 252kV, to cut offrated current , faulty current, or switching lines, to control and protectthe power system, can also be used as a contact circuit breaker.SF6 gas is used as an arc extinguishing and insulating medium,using the most advanced self- powered arc extinguishing technologyin the world. With a new spring operating mechanism, it has thecharacteristics of long life, low operation, low noise, highreliability.It’s simple structure, small size, long period of free maintenance.In the current process of power equipment becoming oil- free andlarge capacity, it can completely replace the same type of imported products.


Product Detail

Product Tags

Product Overview
    LW □ -252/4000-50 self-energy AC high-voltage sulfur hexachloride circuit breaker for outdoor products, applicable toaltitude not exceeding 2000 m, ambient temperature not less than-30 ℃ , AC 50 Hz of the area where the pollution level is not higher than level IV, in the grid with a maximum voltage of 252kV, to cut offrated current , faulty current, or switching lines, to control and protectthe power system, can also be used as a contact circuit breaker.

    SF6 gas is used as an arc extinguishing and insulating medium,using the most advanced self- powered arc extinguishing technologyin the world. With a new spring operating mechanism, it has thecharacteristics of long life, low operation, low noise, highreliability.It’s simple structure, small size, long period of free maintenance.In the current process of power equipment becoming oil- free andlarge capacity, it can completely replace the same type of imported products.
Main Technical Parameters

No. Item Unit Data
1  Rated voltage   252
2 Rated power frequency withstand voltage(1min) To earth kV 460
Fracture 460+146
3 Rated lightning impulse withstand voltage To earth 1050
Fracture 1050+206
4 Rated frequency Hz 50
5 Rated current A 4000
6 First-pole-to-clear factor   1.3
7 Rated short-circuit breaking current kA 50
8 Rated short circuit closing current (peak) kA 125
9 Rated short circuit withstand current kA 50
10 Rated peak withstand current 125
11 Rated short circuit duration s 3
12 Rated out-of-step breaking current kA 12.5
13 Near fault breaking current kA 90%lk,75%lk
14 Rated line charging opening and closing current A 200
15 Rated operation sequence   0-0.3s-CO-180s-CO
16 Main circuit resistance μΩ ≤ 55
17 Rated sulfur hexafluoride gas pressure (20℃ gauge pressure) Mpa 0.6
18 Alarm/minimum functional pressure (20℃ gauge pressure) Mpa 0.55±0.015/0.50±0.015
19 Annual air leakage rate of SF6 gases   ≤ 0.5%
20 Gas moisture content (V/V) ppm ≤ 150
21 Mechanical life   6000
22 Radio interference level μV < 500
23 Creepage distance Fracture mm ≥ 8660
To earth ≥ 6900
24 Weight of SF6 gas per unit kg 24
25 Weight of circuit breakers per phase kg 1500

Appearance And Installation Dimensions


  • Previous:
  • Next:

  • Write your message here and send it to us