LN22 HIGH VOLTAGE SULFUR HEXAFLUORIDE CIRCUIT BREAKER

Short Description:

  • Application and Compatibility:
    • Suitable for three-phase AC 50Hz systems.
    • Rated voltage of 40.5kV, making it suitable for industrial and mining enterprises, power plants, and substations.
    • Capable of handling load current, overload current, and fault current interruptions.

 

  • Design and Construction:
    • Compact Design: Utilizes an upper and lower layout structure to reduce overall depth.
    • Insulation: Features a composite insulation structure using epoxy resin cylinders to isolate the arc extinguishing chamber and charged components.
    • Electrical Connections: Utilizes fixed connections for the main circuit, ensuring high reliability.
    • Phase Spacing: Achieves a narrow phase spacing of only 300mm, enhancing compactness.

 

  • Operating Mechanism:
    • Spring Operating Mechanism: Specifically designed for this circuit breaker type, installed within the frame to optimize the upper and lower layout.
    • Performance: Provides output curve and performance suitable for 40.5kV vacuum circuit breakers.

 

  • Performance and Maintenance:
    • Reliability: Offers reliable electrical performance suitable for frequent operations.
    • Longevity: Designed for a long service life with minimal maintenance requirements.
    • Environmental Suitability: Suitable for harsh operating conditions.

 

  • Overall Features:
    • Size and Appearance: Small size with a reasonable, aesthetically pleasing layout.
    • Operation: Flexible operation and simplified structural design.
    • Maintenance: Convenient maintenance procedures with a mechanism designed to be maintenance-free.


Product Detail

Product Tags

Product Overview

    LN22 indoor high-voltage sulfur hexafluoride circuit breaker (hereinafter referred to as circuit breaker) is suitable for three-phase AC 50Hz, rated voltage 40.5kV power system, and can be used for breaking load current, overload current, and fault current in industrial and mining enterprises, power plants, and substations.
    The circuit breaker and operating mechanism adopt an upper and lower layout structure, effectively reducing the depth of the circuit breaker.
    The three-phase arc extinguishing chamber and the connected charged body are isolated by three independent epoxy resin insulation cylinders, forming a composite insulation structure. The circuit breaker meets the air distance and creep distance requirements under normal operating conditions and effectively reduces the volume of the circuit breaker. The main electrical circuit vacuum arc extinguishing chamber and the dynamic static conductive connection are installed inside the insulation cylinder, so that the phase spacing is only 300mm. The electrical connections of the main circuit are all fixed connections, which have high reliability. The insulation cylinder is installed above the circuit breaker frame.
    The spring operating mechanism specially designed for this new type of circuit breaker is installed within the circuit breaker frame, and its structural characteristics are more suitable for the upper and lower layout of the circuit breaker, becoming an integral part of the overall structure of the circuit breaker. The structure design is simple, and the output curve and performance are more suitable for the characteristics and requirements of 40.5kV vacuum circuit breakers.
    The overall layout is reasonable, beautiful, and concise. Small size, flexible operation, reliable electrical performance, long service life, convenient maintenance, and maintenance free mechanism.
This circuit breaker is suitable for frequent operation, various occasions, and places with harsh operating conditions.

 

Main Technical Parameters

 Item  Unit Data
 Rated voltage kV 40.5
1 min Power frequency withstand voltage (valid value) kV 95
Lightning impulse withstand voltage (peak) kV 185
 Rated frequency Hz 50
 Rated current A 630,1250, 1600, 2000
Rated short-time withstand current kA 25, 31.5
 Rated peak withstand current kA 63, 80
 Rated short circuit duration s 4
Rated short-circuit breaking current kA 25, 31.5
 Rated short circuit switching current kA 63, 80
 Rated operation sequence   O-0.3s-CO-180s-CO
 Breaking duration ms <80
 Rated short circuit breaking current breaking times  Times 30
 rated operation voltage V AC110, 220; DC110,220
 Mechanical life  Times 10000