LN2-40.5 type sulfur hexafluoride circuit breaker is a three-phase AC 50HZ indoor device, which can be used for protection and controlling of industrial and mining enterprises, power plants and substations, and can be used in frequent operation places, and can also be used for contact circuit breakers. And can fit the capacitor bank.LN2-40.5 type circuit breaker is equipped with 3AF type spring operating mechanism handcart, which is specially configured in KYN61-40.5 type metal enclosed switch cabinet.


Product Detail

Product Tags

Product Overview
    LN2-40.5 type sulfur hexafluoride circuit breaker is a three-phase AC 50HZ indoor device, which can be used for protection and controlling of industrial and mining enterprises, power plants and substations, and can be used in frequent operation places, and can also be used for contact circuit breakers. And can fit the capacitor bank.

   LN2-40.5 type circuit breaker is equipped with 3AF type spring operating mechanism handcart, which is specially configured in KYN61-40.5 type metal enclosed switch cabinet.
Structural properties
The arc extinguishing chamber of LN2-40.5 type circuit breaker is a self-energy rotary arc expansion type, which comprehensively applies the principle of rotary arc blowing and the principle of air compression for arc extinguishing, and has good arc extinguishing performance.
LN2-40.5 type circuit breaker has good breaking performance , long maintenance period, long electrical life, short arcing time, no operating overvoltage, high mechanical reliability, and can withstand the highest working voltage for 10 minutes at zero gauge voltage, and can be broken It is your ideal high- voltage electrical product without overhaul
Main Technical Parameters

 No.  Item  Unit  Data
1 Voltage  Rated kV 35
 Maximum 40.5
2 Rated insulation level Lightning shock withstand voltage (full wave) kV 185
 Power frequency voltage 95
3 Rated current A 1000
4  Rated breaking current kA 25
5  Rated closing current kA 63
6  Dynamic stability current kA( Peak value) 63
7 Thermal stability current (time) kA( Valid value) 25 (4S)
8  Rated out-of-step breaking current 6.5
9 Electrical life  Breaking rated current Times 3000
 Rated current breaking times 16
10 Closing time (not greater than) s 0.15
11 Opening time (not greater than) s 0.06
12  Breaking current of Breaking capacitor bank A 800
13  Mechanical life  Times 6000
14

Rated pressure

20℃ Mpa 0.65

Signal pressure

0.62

Blocking pressure

0.59
15  Annual air leakage rate (not greater than)   1%
16  Moisture content PPm(V) 150
17 Weight  Circuit breaker body kg 135
SF6  gas 1.5