Welcome to our websites!
Tel/Whatsapp/Wechat: +86-15968734813, Email: alice@cnhighvolt.com

GW23-126、252 SINGLE-ARM FOLDING HORIZONTAL RETRACTABLE OUTDOOR HIGH- VOLTAGE AC DISCONNECTING SWITCH

Short Description:

GW23-252 high-voltage disconnecting switch is a two-post horizontal telescopic three-phase AC 50Hz outdoor high-voltage switchgear.It isused in power systems with a rated voltage of 252kV. It is used for switching operations under no-load conditions, and for electrical equipment and For electrical isolation between live circuits.The product complies with GB1985 and IEC62271-102 standards


Product Detail

Product Tags

Product Overview
   GW23-252 high-voltage disconnecting switch is a two-post horizontal telescopic three-phase AC 50Hz outdoor high-voltage switchgear.It isused in power systems with a rated voltage of 252kV. It is used for switching operations under no-load conditions, and for electrical equipment and For electrical isolation between live circuits.

    The product complies with GB1985 and IEC62271-102 standards
Working Environment
1. The altitude does not exceed: 2000m
2. Ambient temperature: -40℃ ~+40℃
3. Maximum wind speed: 34m/s 4. Anti-seismic ability: horizontal acceleration: 0.250g; vertical:0.125g acceleration: 0.125g
5.10mm 5. The thickness of icing does not exceed 10mm
6. Insulator pollution level: Ⅲ (25mm/kV), Ⅳ (31mm/kV)
7. There should be no flammable,explosive, chemical corrosion and be no frequent and severe vibrations

Main Technical Parameters

No. Item Unit Data
1 Rated voltage kV 252
2 Rated current A 3150
3 Rated short-time withstand current kA 50
4 Rated peak withstand current kA 125
5 Rated short time power frequency voltage To earth kV 460
Fracture 460+145
6 Rated lightning impact voltage To earth kV 1050
Fracture 1050+200
7 Terminal rated pull force Longitudinal N 1500
Horizontal 1000
Vertical 1250
8 Bending Failure Load of Pillar Insulator N 8000
 9 Grounding switch induced current switching capability test Electromagnetic coupling Rated inductive current A 80
Rated inductive voltage kV 1.4
Electrostatic coupling Rated inductive current A 1.25
Rated inductive voltage kV 5
10 Open and close bus conversion current A 1600
11 Mechanical life Times 3000
12 Single pole weight of disconnecting switch kg 1050

Appearance And Installation Dimensions

 

 


  • Previous:
  • Next: