GW -12(15/24) HIGH VOLTAGE DISCONNECTING SWITCH

Short Description:

GW □ – 12 (15 / 24) outdoor high-voltage disconnector is a 50 Hz AC outdoor high-voltage electrical equipment, with rated voltage levels of 10 kV, 15 kV and 24 kV. It is used for opening and closing of high-voltage lines under no-load condition, and for electrical isolation of live high-voltage lines of electrical equipment such as high-voltage bus and circuit breaker under repair. It can also be used for opening and closing small capacitive or inductive current.This series of outdoor disconnectors meet the relevant provisions of GB 1985 “AC high voltage disconnectors and earthing switches”, IEC 60129 “AC disconnectors and earthing switches” and GB / t11022 “common technical requirements for standards of high voltage switchgear and control equipment”


Product Detail

Product Tags

Product Overview
   GW □ – 12 (15 / 24) outdoor high-voltage disconnector is a 50 Hz AC outdoor high-voltage electrical equipment, with rated voltage levels of 10 kV, 15 kV and 24 kV. It is used for opening and closing of high-voltage lines under no-load condition, and for electrical isolation of live high-voltage lines of electrical equipment such as high-voltage bus and circuit breaker under repair. It can also be used for opening and closing small capacitive or inductive current.

    This series of outdoor disconnectors meet the relevant provisions of GB 1985 “AC high voltage disconnectors and earthing switches”, IEC 60129 “AC disconnectors and earthing switches” and GB / t11022 “common technical requirements for standards of high voltage switchgear and control equipment”

Main Technical Parameters

Item Unit  
Rated voltage kV 10 12 20
Maximum operating voltage kV 12 12 24
Rated insulation level 1 minute power frequency withstand voltage (RMS) To the ground kV 40 40 65
fracture kV 47 47 79
Lightning impulse withstand voltage (peak value) To the ground kV 105 105 125
fracture kV 120 120 145
Rated frequency Hz 50
Rated current A 200 400 630 800 1000 1250
4 second thermal stability current (RMS) kA 6.3 12.5 20 25 25 31.5
Dynamic stability current (peak value) kA 16 31.5 50 63 63 80
Creepage distance mm 300   380
Mechanical life time 2000   2000

Appearance And Installation Dimensions


  • Previous:
  • Next:

  • Write your message here and send it to us