FKN12-12D/T630-20 FKRN12-12D/T125-31.5 INDOOR HIGH VOLTAGE PNEUMATIC LOAD SWITCH

Short Description:

FKN12-12D/T630-20 FKRN12-12D/T125-31.5 indoor high- voltage compressed air load switch is suitable for three- phase high-voltage switchgear of 12KV and below, as the control and protection of power equipment such as transformers, cables, overhead lines, etc. ; Especially suitable for terminal substations and box-type substations of urban and rural networks. It is also suitable for the control and protection of ring network and dual radiation power supply units.


Product Detail

Product Tags

Product Overview

   FKN12-12D/T630-20 FKRN12-12D/T125-31.5 indoor high- voltage compressed air load switch is suitable for three- phase high-voltage switchgear of 12KV and below, as the control and protection of power equipment such as transformers, cables, overhead lines, etc. ; Especially suitable for terminal substations and box-type substations of urban and rural networks. It is also suitable for the control and protection of ring network and dual radiation power supply units.

Main Technical Parameters
No. Item Unit  Data
FKN12-12D FKRN12-12D
1  Rated voltage kV 12
2  Rated frequency Hz 50
3  Rated current A 630 1250
4  Lightning impulse withstand voltage kV to earth and interphase 42,isolating fracture 48
5  1 min Power frequency withstand voltage kV to earth and interphase 75,isolating fracture 85
6 Rated short-time withstand current  load switch kA 20 -
 grounding switch kA 20
7 Rated short circuit duration  load switch s 4  
 grounding switch s 2
8 Rated short-circuit closing current (peak)   50 -
  9  Rated breaking current Active load breaking current A 630 -
 Closed-loop breakingg current A 630 -
5% Rated active load breaking current A 31.5 -
 Cable charging current A 10 -
Breaking no-load transformer capacity KVA 1250
10 Rated short circuit breaking current (current limiting fuse) KA - 31.5
11  Rated transfer current A - 1200
12 Mechanical life  Times 2000 2000
13 Impactor output energy J J 1+0.5

Appearance And Installation Dimensions

 

 